K0374 K374: Install smoke barrier doors that can resist smoke for at least 20 minutes.
E

Smoke Barrier Door Hardware Failed to Latch Properly

Spiritrust Lutheran The Village At GettysburgGettysburg, Pennsylvania Survey Completed on 06-25-2025

Summary

During an observation, surveyors found that the double smoke barrier door located between compartments AA and AE did not latch properly when closed. The latching hardware on this smoke barrier door failed to function according to manufacturer specifications. This issue was confirmed in an interview with the Director of Facilities, who acknowledged that the smoke barrier door hardware was not operating as required. The deficiency affected two out of ten smoke compartments within the component. No information regarding residents' medical history or condition at the time of the deficiency was provided in the report.

Plan Of Correction

Hardware will be repaired and adjusted on smoke barrier doors between compartments AA and AE. A recurring work order will be created to inspect doors for proper operation and positive latching quarterly for one year. Completed work order documentation will be presented to QAPI for evaluation.

Penalty

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
See other K0374 citations
Failure to Maintain Smoke Barrier Doors to Resist Passage of Smoke
E
K0374 K374: Install smoke barrier doors that can resist smoke for at least 20 minutes.
Short Summary

Surveyors identified that smoke barrier doors in two areas of the facility were not maintained to resist the passage of smoke. In one hallway outside a nurse's station, the smoke barrier doors did not close smoke-tight because the door frame was unsecured within the wall. In another area outside the lobby, the smoke barrier doors failed to swing and close smoke-tight due to a broken door closer, and this problem remained uncorrected at a later revisit survey, as confirmed by the Administrator and Maintenance Director.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Smoke Barrier Doors Failed to Close Smoke-Tight
E
K0374 K374: Install smoke barrier doors that can resist smoke for at least 20 minutes.
Short Summary

Smoke barrier doors near the Laundry Area did not fully close when released from hold-open devices, resulting in a failure to maintain smoke-tight conditions as required. Facility leadership confirmed the deficiency during the survey.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Smoke Barrier Doors Failed to Self-Close and Latch
E
K0374 K374: Install smoke barrier doors that can resist smoke for at least 20 minutes.
Short Summary

Surveyors observed that smoke barrier doors near a third-floor room failed to self-close and latch when tested, affecting two smoke compartments. Facility leadership confirmed the deficiency.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Failure of Fire/Smoke Barrier Doors to Close as Required
E
K0374 K374: Install smoke barrier doors that can resist smoke for at least 20 minutes.
Short Summary

Surveyors found that several fire/smoke barrier doors, including those near the DON office and in resident rooms, were unable to close properly during both routine checks and a fire alarm test. Staff confirmed they were unaware of the closure requirements for these doors, resulting in noncompliance with NFPA 101-2012 standards and potentially affecting multiple residents.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Smoke Barrier Doors Failed to Achieve Smoke-Tight Fit
F
K0374 K374: Install smoke barrier doors that can resist smoke for at least 20 minutes.
Short Summary

Surveyors observed that smoke barrier doors near a resident room and by a nurses station leading to the dining room did not fully close and latch to a smoke-tight fit as required by LSC. The Maintenance Director confirmed these findings.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Smoke Barrier Doors Failed to Close During Fire Alarm Testing
F
K0374 K374: Install smoke barrier doors that can resist smoke for at least 20 minutes.
Short Summary

Surveyors found that smoke barrier doors in three compartments did not release from magnetic holders and close during fire alarm testing, despite activation of smoke detectors, pull stations, and waterflow tests. Staff and a vendor had differing understandings of the door operation, and the malfunction affected all residents in the affected areas.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.

Know what gets cited — and walk into your next survey with full visibility

We process and analyze inspection reports and Plans of Correction using AI to surface insights and trends — so you can improve care quality and stay ahead of compliance risk before your next survey.

Get ready for your next survey

See what surveyors are citing in your state and spot your risk areas before they do.

Monthly Citation Reports

Have you been cited for this tag?

Save hours drafting a compliant Plan of Correction — AI built on real approved POCs.

Plan of Correction Writer

Trusted data from CMS and state health departments

Every citation, penalty and Plan of Correction is sourced from public CMS records (latest release June 24, 2026) and official state health department websites — never guesswork.

Trusted by long-term care providers and associations.

Allegria Senior Living logo
FHCA logo
WeCare Centers logo
Care Rehab logo
An unhandled error has occurred. Reload 🗙