K0511 K511: Have properly installed electrical wiring and gas equipment.
D

Deficient Maintenance of Sprinkler Systems and Improper Storage in Electrical Panel Room

Bel Vista Healthcare CenterLong Beach, California Survey Completed on 05-19-2025

Summary

Surveyors observed multiple deficiencies related to the maintenance of fire safety equipment and electrical panel access. During several walkthroughs with the maintenance supervisor (MS), it was noted that sprinkler deflectors in various rooms, including resident rooms, a restroom, and a shower room, had significant buildups of dust and, in one case, a green mildew-like substance. The MS acknowledged these findings during the observations. The facility's maintenance policy states that the maintenance department is responsible for keeping the building and equipment in a safe and operable manner and in compliance with applicable regulations. Additionally, the electrical panel room was found to be used for storage and as an office space for the case manager. Items such as binders, blank paper, and a floor polishing machine were stored within three inches of the electrical panel, which is not compliant with NFPA 70 requirements for clear working space around electrical panels. The MS confirmed that the room had been used in this manner for years due to limited space in the building and acknowledged the findings during the survey.

Plan Of Correction

BEL VISTA HEALTHCARE CENTER makes every effort to operate in substantial compliance with Federal and State laws and regulations. Nothing in this Plan of Correction is an admission otherwise. BEL VISTA HEALTHCARE CENTER is submitting this Plan of Correction in compliance with its regulatory obligations and does not waive any objections it may have as to the merit or form of any allegations contained herein. Please note that the facility may contest the merits or form of any of the alleged deficient findings and may take reasonable steps to appeal them. This Plan of Correction constitutes BEL VISTA HEALTHCARE CENTER's written credible allegation of compliance for the deficiencies noted. It is the facility's policy to comply with all applicable federal and state regulations regarding electrical safety requirements as specified in NFPA 101 Life Safety Code (2012 Edition) and NFPA 70 National Electrical Code (2011 Edition), specifically regarding maintaining clear working spaces around electrical panels. Corrective Action Taken: On 05/20/2025, the Maintenance Supervisor immediately removed all stored items, including binders, paper, and floor polishing machine from the electrical panel room. The Case Manager's office was relocated to an alternative space within the facility. The electrical panel room was secured with appropriate signage indicating "Electrical Room - No Storage Permitted." The Maintenance Supervisor conducted a complete inspection of all electrical panel rooms facility-wide to ensure compliance with NFPA requirements for clear working spaces. Identification of Other Areas with Potential to be Affected: The Maintenance Supervisor, in conjunction with the Safety Committee, completed a facility-wide assessment on 05/20/2025 to identify any other electrical panels or utility rooms that could potentially be affected by improper storage or space utilization. This assessment included all four smoke compartments and documentation of current space utilization near all electrical equipment. Systemic Changes and Measures Implemented: 1. The facility's Maintenance Service Policy and Procedure has been revised to specifically address electrical room safety requirements, including: • Prohibition of storage within 36 inches of electrical panels • Required monthly inspections of all electrical rooms and panels 2. Implementation of a facility-wide space utilization assessment to ensure appropriate allocation of office and storage areas. Monitoring and Quality Assurance: The Maintenance Director will conduct weekly inspections of all electrical rooms for the first month, then monthly thereafter. The Director of Maintenance will conduct independent monthly audits to ensure continued compliance. Results will be documented and reviewed during monthly Safety Committee meetings and quarterly QAPI meetings. The QAPI Committee will monitor compliance until substantial compliance is achieved and maintained for three consecutive quarters. Any identified issues will

Penalty

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
See other K0511 citations
Improper Fastening of Circuit Breaker Panel Cover with Sheet Metal Screws
D
K0511 K511: Have properly installed electrical wiring and gas equipment.
Short Summary

Surveyors found that a circuit breaker panel cover in one smoke compartment was improperly fastened with sheet metal screws instead of appropriate blunt-end fasteners, in violation of NFPA 70 requirements. The maintenance director acknowledged the use of sheet metal screws on the panel cover, and the report notes that this noncompliance could result in electric or fire hazards.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Improperly Labeled and Maintained Electrical Panels
F
K0511 K511: Have properly installed electrical wiring and gas equipment.
Short Summary

Surveyors identified that the facility’s electrical system was not maintained according to NFPA 101 and NFPA 70. In the kitchen electrical panel, breakers labeled for the dishwasher were in the off position while the dishwasher continued to run with power. In generator sub panel B, a breaker was labeled for a sprinkler pump even though no sprinkler pump existed, and there was an open breaker position without a blank cover. These issues were confirmed by the Maintenance Director and had the potential to affect all residents.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Non-GFCI Electrical Outlet Near Sink in Medication Room
D
K0511 K511: Have properly installed electrical wiring and gas equipment.
Short Summary

Surveyors observed that an electrical outlet in Nursing Station 1's med room was installed 18 inches from a sink and was not equipped with a required ground-fault circuit interrupter (GFCI), as mandated by NFPA 70, National Electrical Code. The DES confirmed during the survey that this outlet lacked GFCI protection, resulting in a cited deficiency related to utilities and electrical safety in one of the facility’s smoke compartments.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Exposed Electrical Wiring Due to Missing Junction Box Cover
E
K0511 K511: Have properly installed electrical wiring and gas equipment.
Short Summary

An electrical junction box above the Zone 8 suspended ceiling, near the smoke barrier doors by the Unit Scheduler's Office, was found without a cover plate, leaving electrical wiring exposed. The Director of Maintenance confirmed the issue during the inspection.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Noncompliance with Gas and Electrical Safety Standards
F
K0511 K511: Have properly installed electrical wiring and gas equipment.
Short Summary

Surveyors observed multiple deficiencies including broken light bulb bases left in ceiling sockets, combustible materials stored too close to electrical panels, and exposed wiring behind a boiler. These issues were confirmed by facility leadership during the inspection.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Broken Electrical Outlet Faceplate at Nurse Station
D
K0511 K511: Have properly installed electrical wiring and gas equipment.
Short Summary

An electrical outlet at Nurse Station #2 was found with a broken faceplate, exposing metal terminals. The CMO confirmed the damage had not been previously noticed. Facility policy assigns the Maintenance Director responsibility for maintaining safe equipment, but the exposed outlet was not addressed as required by NFPA 70.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.

Know what gets cited — and walk into your next survey with full visibility

We process and analyze inspection reports and Plans of Correction using AI to surface insights and trends — so you can improve care quality and stay ahead of compliance risk before your next survey.

Get ready for your next survey

See what surveyors are citing in your state and spot your risk areas before they do.

Monthly Citation Reports

Have you been cited for this tag?

Save hours drafting a compliant Plan of Correction — AI built on real approved POCs.

Plan of Correction Writer

Trusted data from CMS and state health departments

Every citation, penalty and Plan of Correction is sourced from public CMS records (latest release June 24, 2026) and official state health department websites — never guesswork.

Trusted by long-term care providers and associations.

Allegria Senior Living logo
FHCA logo
WeCare Centers logo
Care Rehab logo
An unhandled error has occurred. Reload 🗙