K0923 K923: Have proper medical gas storage and administration areas.
E

Failure to Post Required Oxygen Storage Room Cautionary Signage

River's Edge Rehabilitation & Healthcare CenterPhiladelphia, Pennsylvania Survey Completed on 04-28-2026

Summary

Surveyors identified a deficiency related to NFPA 101 and NFPA 99 requirements for gas equipment cylinder and container storage. During an observation on the second floor, they found that the Oxygen Storage Room did not have the required precautionary signage on the door. Specifically, the room lacked a sign readable from 5 feet that stated: "CAUTION: OXIDIZING GAS(ES) STORED WITHIN NO SMOKING," as required for oxygen cylinder storage areas. This absence was directly observed by surveyors during the inspection. In an exit interview conducted with the Administrator and the Maintenance Director following the initial observation, facility leadership confirmed the lack of required signage. During a subsequent onsite revisit, surveyors again observed that the same second-floor Oxygen Storage Room still lacked the mandated cautionary sign. In a second exit interview with the Administrator and a Maintenance Representative, they again confirmed that the signage remained absent at the time of the revisit.

Plan Of Correction

1. The facility immediately purchased and installed the required signage at the Oxygen Storage Room on the second floor. The signage was updated to include "Oxygen Storage No Smoking" in accordance with NFPA 99 requirements for compressed gas storage areas. 2. All residents have the potential to be affected by this issue. 3. The Director of Maintenance and facility leadership were in-serviced on the requirements for proper labeling and signage of medical gas storage areas, including oxygen storage rooms, in accordance with NFPA 99 and CMS Life Safety Code requirements. 4. The Director of Maintenance or designee will conduct routine environmental rounds to ensure all medical gas storage areas are properly labeled and compliant with NFPA 99 signage requirements. Audits will be conducted monthly for three months, with immediate correction of any identified deficiencies. Findings will be documented and reported to the Quality Assurance and Performance Improvement (QAPI) Committee as appropriate.

Penalty

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
See other K0923 citations
Failure to Maintain Required Oxygen Cylinder Storage and Secured Storage Room
E
K0923 K923: Have proper medical gas storage and administration areas.
Short Summary

Surveyors found that oxygen storage requirements were not maintained when a freestanding oxygen cylinder was observed unsecured in a third-floor room and the C-Hall oxygen storage room door failed to close and latch due to a coordinator malfunction. The Maintenance Director confirmed these oxygen storage deficiencies during the survey exit interview.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Improper Storage of Oxygen Cylinders Near Combustibles
F
K0923 K923: Have proper medical gas storage and administration areas.
Short Summary

Surveyors observed that more than 12 "E" oxygen cylinders (18 total) were stored in a sprinkler room within five feet of combustible materials, contrary to NFPA 99 requirements for gas equipment cylinder storage. The Maintenance Director confirmed this storage practice during the survey. This noncompliance with NFPA 99 sections 11.3.1–11.3.3 was cited as a deficiency affecting all occupants in the event of a fire or other emergency.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Failure to Post Required Oxygen Storage Signage in Crash Cart Rooms
E
K0923 K923: Have proper medical gas storage and administration areas.
Short Summary

Surveyors found that oxygen cylinders were stored in crash cart rooms in two separate cores without the required precautionary signage on the doors indicating oxidizing gas storage and no smoking. Observations in two smoke compartments showed oxygen cylinders present in the 3 East and 2 East core crash cart rooms, yet the doors lacked the mandated "CAUTION: OXIDIZING GAS(ES) STORED WITHIN NO SMOKING" signage. The facility administrator and maintenance leadership confirmed that the proper oxygen storage signs were not posted on these doors.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Improper Oxygen Cylinder Storage Near Combustibles and Electrical Receptacles
E
K0923 K923: Have proper medical gas storage and administration areas.
Short Summary

Surveyors found that oxygen cylinders stored within first- and second-floor nurses' stations were placed less than five feet from electrical receptacles and combustible materials, in violation of NFPA 99/101 requirements for separation of oxidizing gases from combustibles and ignition sources. The Administrator and Maintenance Director confirmed during interview that the cylinders were improperly stored in proximity to these combustible and ignition sources.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Improper Storage and Security of Gas Cylinders
D
K0923 K923: Have proper medical gas storage and administration areas.
Short Summary

Surveyors found that gas cylinders were improperly stored and unsecured, with 38 cylinders in an outside storage room lacking the required oxidizing gas signage and with full and empty cylinders comingled, and an additional 25 cylinders stored adjacent to this area without any means to prevent unauthorized access. During an interview, the Maintenance Director acknowledged the issues and reported being unaware of the specific NFPA 99 storage requirements.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Improper Oxygen Cylinder Storage Exceeding 300 Cubic Feet
D
K0923 K923: Have proper medical gas storage and administration areas.
Short Summary

Surveyors found that more than 12 E-sized oxygen cylinders, exceeding 300 cubic feet, were improperly stored in the basement activities room. The storage did not meet NFPA requirements for construction, ventilation, and separation, as confirmed by the maintenance supervisor.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.

Know what gets cited — and walk into your next survey with full visibility

We process and analyze inspection reports and Plans of Correction using AI to surface insights and trends — so you can improve care quality and stay ahead of compliance risk before your next survey.

Get ready for your next survey

See what surveyors are citing in your state and spot your risk areas before they do.

Monthly Citation Reports

Have you been cited for this tag?

Save hours drafting a compliant Plan of Correction — AI built on real approved POCs.

Plan of Correction Writer