K0923 K923: Have proper medical gas storage and administration areas.
F

Improper Storage of Oxygen Cylinders Near Combustibles

Glades Health Care CenterPahokee, Florida Survey Completed on 04-29-2026

Summary

The deficiency involves improper storage of medical gas cylinders, specifically more than 12 "E" oxygen tanks, in violation of NFPA 99 requirements. During an observation at 4:30 PM with the Maintenance Director, surveyors noted that 18 "E" tanks were being stored in a sprinkler room. These cylinders were located within five feet of combustible materials, contrary to NFPA 99 (2012 and 2021 editions), which requires that oxidizing gas cylinders in quantities greater than 300 cubic feet be separated from combustibles by at least 20 feet (or 5 feet if the area is sprinklered) or stored in an appropriately rated noncombustible cabinet. The report states that the storage arrangement did not comply with NFPA 99 sections 11.3.1, 11.3.2, and 11.3.3, which govern gas equipment cylinder and container storage, including separation from combustibles. The Maintenance Director acknowledged during the survey that 18 "E" tanks were stored in the sprinkler room within five feet of combustibles. The deficiency is cited as affecting all occupants in the facility in the event of a fire or other emergency, and no additional resident-specific clinical details are provided in the report.

Plan Of Correction

tank cylinders were removed from certain locations and the number of tanks were reduced in those locations. The tanks were relocated to a locked designated area. This was completed on . [R] tank cylinders were removed from certain locations and the number of tanks were reduced in those locations. The tanks were relocated to a locked designated area. This was completed on [R] . The facility has determined that all residents have the potential to be affected. An in-service education program will be conducted by the administrator. The administrator will conduct for a period of three months a random audit of completed documentation.

Penalty

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
See other K0923 citations
Failure to Maintain Required Oxygen Cylinder Storage and Secured Storage Room
E
K0923 K923: Have proper medical gas storage and administration areas.
Short Summary

Surveyors found that oxygen storage requirements were not maintained when a freestanding oxygen cylinder was observed unsecured in a third-floor room and the C-Hall oxygen storage room door failed to close and latch due to a coordinator malfunction. The Maintenance Director confirmed these oxygen storage deficiencies during the survey exit interview.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Failure to Post Required Oxygen Storage Room Cautionary Signage
E
K0923 K923: Have proper medical gas storage and administration areas.
Short Summary

Surveyors found that an oxygen storage room on the second floor lacked the required precautionary signage stating, "CAUTION: OXIDIZING GAS(ES) STORED WITHIN NO SMOKING," as mandated for gas cylinder storage areas. This deficiency was confirmed by facility leadership during the initial survey and again during a subsequent revisit, when the same room was still missing the required sign.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Failure to Post Required Oxygen Storage Signage in Crash Cart Rooms
E
K0923 K923: Have proper medical gas storage and administration areas.
Short Summary

Surveyors found that oxygen cylinders were stored in crash cart rooms in two separate cores without the required precautionary signage on the doors indicating oxidizing gas storage and no smoking. Observations in two smoke compartments showed oxygen cylinders present in the 3 East and 2 East core crash cart rooms, yet the doors lacked the mandated "CAUTION: OXIDIZING GAS(ES) STORED WITHIN NO SMOKING" signage. The facility administrator and maintenance leadership confirmed that the proper oxygen storage signs were not posted on these doors.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Improper Oxygen Cylinder Storage Near Combustibles and Electrical Receptacles
E
K0923 K923: Have proper medical gas storage and administration areas.
Short Summary

Surveyors found that oxygen cylinders stored within first- and second-floor nurses' stations were placed less than five feet from electrical receptacles and combustible materials, in violation of NFPA 99/101 requirements for separation of oxidizing gases from combustibles and ignition sources. The Administrator and Maintenance Director confirmed during interview that the cylinders were improperly stored in proximity to these combustible and ignition sources.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Improper Storage and Security of Gas Cylinders
D
K0923 K923: Have proper medical gas storage and administration areas.
Short Summary

Surveyors found that gas cylinders were improperly stored and unsecured, with 38 cylinders in an outside storage room lacking the required oxidizing gas signage and with full and empty cylinders comingled, and an additional 25 cylinders stored adjacent to this area without any means to prevent unauthorized access. During an interview, the Maintenance Director acknowledged the issues and reported being unaware of the specific NFPA 99 storage requirements.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Improper Oxygen Cylinder Storage Exceeding 300 Cubic Feet
D
K0923 K923: Have proper medical gas storage and administration areas.
Short Summary

Surveyors found that more than 12 E-sized oxygen cylinders, exceeding 300 cubic feet, were improperly stored in the basement activities room. The storage did not meet NFPA requirements for construction, ventilation, and separation, as confirmed by the maintenance supervisor.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.

Know what gets cited — and walk into your next survey with full visibility

We process and analyze inspection reports and Plans of Correction using AI to surface insights and trends — so you can improve care quality and stay ahead of compliance risk before your next survey.

Get ready for your next survey

See what surveyors are citing in your state and spot your risk areas before they do.

Monthly Citation Reports

Have you been cited for this tag?

Save hours drafting a compliant Plan of Correction — AI built on real approved POCs.

Plan of Correction Writer

Trusted data from CMS and state health departments

Every citation, penalty and Plan of Correction is sourced from public CMS records (latest release June 24, 2026) and official state health department websites — never guesswork.

Trusted by long-term care providers and associations.

Allegria Senior Living logo
FHCA logo
WeCare Centers logo
Care Rehab logo
An unhandled error has occurred. Reload 🗙