K0281 K281: Install proper backup exit lighting.
E

Failure to Provide Automatic Emergency Illumination

Our Ladys Center For Rehabilitation & HealthcarePleasantville, New Jersey Survey Completed on 12-31-2024

Summary

The facility failed to provide emergency illumination that would operate automatically along the means of egress, as required by NFPA 101:2012 Edition, Sections 19.2.8 and 7.8.1.3* (2). This deficiency was identified during an observation and interview conducted on December 30, 2024, in the presence of U.S. FOIA representatives. Specifically, it was observed that in the C-hall occupied dining room, a single wall light switch controlled all eight ceiling light fixtures, which did not comply with the requirement for emergency illumination to operate automatically. This issue was noted in one of four areas and had the potential to affect 25 residents. The findings were confirmed by the U.S. FOIA representatives at the time of observation and were communicated to the facility during the Life Safety Code survey exit conference on December 31, 2024.

Plan Of Correction

K-0281 (E) NFPA 101- Illumination of Means of Egress 1. The facility is scheduled on January 24, 2025, to install emergency lighting in the dining room to illuminate the discharge path. The room has ambient lighting, and all residents were free from hazards. 2. All remaining egress path lights have been inspected and found at least one light that is on constant power. Fixtures have been tested and are in full operation as of 1/10/2025. All resident areas are free from hazards and all systems are operating as designed. 3. Education is completed with Maintenance staff to confirm proper function and maintenance of all egress path lighting on 1/10/2025. 4. Every quarter for a year the Maintenance Director or designee reviews random exit path lights for function. This information will then be entered on a log and will be presented to the QAPI meeting quarterly for one year. *emergency lighting was installed in the dining room- see attached photo*

Penalty

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
See other K0281 citations
Failure to Ensure Continuous Illumination in Egress Pathway
D
K0281 K281: Install proper backup exit lighting.
Short Summary

The facility did not maintain continuous illumination in the Rehab corridor, as required by NFPA 101 standards. During a survey, it was found that turning off the wall-mounted light switches extinguished all lights in the corridor leading to an emergency stairwell exit. The Director of Maintenance confirmed the issue, noting that the lights would be continuous.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Failure to Illuminate Egress Pathways
E
K0281 K281: Install proper backup exit lighting.
Short Summary

The facility did not provide proper illumination for egress pathways, as required by NFPA 101. Observations revealed that exit doors from the French Quarter wing, the main entrance, and the Spanish Villa wing lacked necessary lighting for safe egress during darkness. These findings were confirmed by the Maintenance Director and acknowledged by the Administrator.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Inadequate Illumination of Egress Pathways
E
K0281 K281: Install proper backup exit lighting.
Short Summary

A Life Safety Code Survey found that the facility did not ensure proper illumination of egress pathways for four of seven exits. Observations revealed a lack of exterior lighting on several sections of the pathways. The Environmental Services Director was unaware of the deficiency but acknowledged the need for additional lighting.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Failure to Ensure Continuous Illumination in Egress Pathway
D
K0281 K281: Install proper backup exit lighting.
Short Summary

The facility did not maintain continuous illumination in the means of egress as required by NFPA 101. During a survey, it was found that turning off the wall-mounted light switches in the fifth-floor dining room also turned off all lights, including those needed for an emergency stairwell exit. This issue was identified on one of the three resident floors, and the Director of Maintenance confirmed the lights would be continuous.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Failure to Maintain Continuous Egress Illumination
E
K0281 K281: Install proper backup exit lighting.
Short Summary

The facility did not maintain continuous illumination of the means of egress in one of five stair towers. Light fixtures failed to illuminate the exit by Component 1, as observed and confirmed by the Director of Maintenance.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Failure to Maintain Illumination in Exit Stairways
E
K0281 K281: Install proper backup exit lighting.
Short Summary

The facility failed to maintain proper illumination in the exit stairways, affecting one of three floors. An observation revealed that the lights in the first floor South main stair tower were not illuminating. This was confirmed during an exit interview with the Administrator and the Maintenance Director.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.

Know what gets cited — and walk into your next survey with full visibility

We process and analyze inspection reports and Plans of Correction using AI to surface insights and trends — so you can improve care quality and stay ahead of compliance risk before your next survey.

Get ready for your next survey

See what surveyors are citing in your state and spot your risk areas before they do.

Monthly Citation Reports

Have you been cited for this tag?

Save hours drafting a compliant Plan of Correction — AI built on real approved POCs.

Plan of Correction Writer

Trusted data from CMS and state health departments

Every citation, penalty and Plan of Correction is sourced from public CMS records (latest release June 24, 2026) and official state health department websites — never guesswork.

Trusted by long-term care providers and associations.

Allegria Senior Living logo
FHCA logo
WeCare Centers logo
Care Rehab logo
An unhandled error has occurred. Reload 🗙