K0281 K281: Install proper backup exit lighting.
D

Failure to Ensure Continuous Illumination in Egress Pathway

Ferncliff Nursing Home Co IncRhinebeck, New York Survey Completed on 02-27-2025

Summary

The facility failed to ensure continuous illumination in the means of egress as required by NFPA 101 standards. During a Life Safety recertification survey, it was observed that the wall-mounted light switches in the fifth-floor dining room, when turned off, extinguished all lights in the room. This room contained an emergency stairwell exit, which should have been continuously illuminated. This deficiency was noted on one of the three resident floors. During an interview, the Director of Maintenance acknowledged the issue and stated that the lights in the rooms would be continuous.

Plan Of Correction

Plan of Correction: Approved March 14, 2025 K281 – NFPA 101 Illumination of Means of Egress I. Immediate Corrections: The manual operated wall mounted light switches in fifth floor dining room were removed, allowing all lights in the room to be on continuously. Work completed (MONTH) 4, 2025. II. Plan of Correction to identify other areas potentially affected The facility acknowledges that all residents have the potential to be affected by this practice. The Director of Plant Operations inspected all areas throughout the facility for the same deficiencies. No additional instances of non-compliant were found. Work completed (MONTH) 6, 2025. III. Systemic Changes The Policy relating to Illumination of Means of Egress was reviewed and it was determined that no changes were needed to the policy. All maintenance staff will be provided with in-service education by the Director of Plant Operations on the policy relating to Illumination of Means of Egress with a focus on the importance of ensuring that Illumination of the Means of Egress were installed and maintained in accordance with 7.8. Work completed: (MONTH) 6, 2025. IV. QA Monitoring The Director of Plant Operations will develop an audit tool to verify that Means of Egress were installed and maintained in accordance with 7.8. 1. Audits will be completed by the Director of Plant Operations monthly x 3 months, then complete quarterly thereafter. 2. Any discrepancies noted will be addressed immediately, reported to the Administrator, and to the QA Committee for tracking and trending. 3. Audit of findings will be presented to QA Committee monthly x 3 months then quarterly thereafter for evaluation and follow-up as indicated. Responsibility: Director of Plant Operations/Designee

Penalty

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
See other K0281 citations
Failure to Ensure Continuous Illumination in Egress Pathway
D
K0281 K281: Install proper backup exit lighting.
Short Summary

The facility did not maintain continuous illumination in the Rehab corridor, as required by NFPA 101 standards. During a survey, it was found that turning off the wall-mounted light switches extinguished all lights in the corridor leading to an emergency stairwell exit. The Director of Maintenance confirmed the issue, noting that the lights would be continuous.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Failure to Illuminate Egress Pathways
E
K0281 K281: Install proper backup exit lighting.
Short Summary

The facility did not provide proper illumination for egress pathways, as required by NFPA 101. Observations revealed that exit doors from the French Quarter wing, the main entrance, and the Spanish Villa wing lacked necessary lighting for safe egress during darkness. These findings were confirmed by the Maintenance Director and acknowledged by the Administrator.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Inadequate Illumination of Egress Pathways
E
K0281 K281: Install proper backup exit lighting.
Short Summary

A Life Safety Code Survey found that the facility did not ensure proper illumination of egress pathways for four of seven exits. Observations revealed a lack of exterior lighting on several sections of the pathways. The Environmental Services Director was unaware of the deficiency but acknowledged the need for additional lighting.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Failure to Maintain Continuous Egress Illumination
E
K0281 K281: Install proper backup exit lighting.
Short Summary

The facility did not maintain continuous illumination of the means of egress in one of five stair towers. Light fixtures failed to illuminate the exit by Component 1, as observed and confirmed by the Director of Maintenance.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Failure to Maintain Illumination in Exit Stairways
E
K0281 K281: Install proper backup exit lighting.
Short Summary

The facility failed to maintain proper illumination in the exit stairways, affecting one of three floors. An observation revealed that the lights in the first floor South main stair tower were not illuminating. This was confirmed during an exit interview with the Administrator and the Maintenance Director.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Failure to Provide Automatic Emergency Illumination
E
K0281 K281: Install proper backup exit lighting.
Short Summary

The facility failed to ensure emergency illumination operated automatically along the means of egress, as required by NFPA 101:2012. In the C-hall dining room, a single wall switch controlled all ceiling lights, affecting 25 residents. This was confirmed by U.S. FOIA representatives during an observation.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.

Know what gets cited — and walk into your next survey with full visibility

We process and analyze inspection reports and Plans of Correction using AI to surface insights and trends — so you can improve care quality and stay ahead of compliance risk before your next survey.

Get ready for your next survey

See what surveyors are citing in your state and spot your risk areas before they do.

Monthly Citation Reports

Have you been cited for this tag?

Save hours drafting a compliant Plan of Correction — AI built on real approved POCs.

Plan of Correction Writer

Trusted data from CMS and state health departments

Every citation, penalty and Plan of Correction is sourced from public CMS records (latest release June 24, 2026) and official state health department websites — never guesswork.

Trusted by long-term care providers and associations.

Allegria Senior Living logo
FHCA logo
WeCare Centers logo
Care Rehab logo
An unhandled error has occurred. Reload 🗙