K0912 K912: Have power receptacles that are properly grounded.
F

Failure to Test Electrical Receptacles Annually

Kittanning Health & Rehab CenterKittanning, Pennsylvania Survey Completed on 01-22-2025

Summary

The facility failed to perform an annual test and inspection on non-hospital grade electrical receptacles in resident sleeping rooms throughout the entire facility. This deficiency was identified during a document review and interview conducted on January 22, 2025. The review revealed that electrical receptacles in resident care rooms were not tested at intervals not exceeding 12 months, as required. The testing should have included a visual inspection of physical integrity, verification of correct polarity of the hot and neutral connections, and ensuring the retention force of the grounding blade was not less than 115g (4 oz). An interview with the maintenance supervisor confirmed the lack of documentation for these tests.

Plan Of Correction

Maintenance immediately tested electrical receptacles. Maintenance to monthly testing of electrical receptacles and maintain documentation according to compliance. NHA/Designee to educate maintenance staff by 21MAR2025 about annual receptacle testing and maintaining proper documentation. NHA/designee to audit monthly x3 for electrical receptacle testing and documentation. Negative findings will be addressed accordingly. Ad Hoc education as needed. The results of the audits will be forwarded to the facility Quality Assurance Performance Improvement (QAPI) committee for further review and recommendations.

Penalty

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
See other K0912 citations
Failure to Maintain GFCI Protection for Electrical Receptacles
B
K0912 K912: Have power receptacles that are properly grounded.
Short Summary

Surveyors identified that three electrical receptacles in the facility were not GFCI protected as required, including those near a sink in the café, a water fountain near the nurse station, and a juice machine in the kitchen. These deficiencies were confirmed by the maintenance supervisor.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Lack of GFCI Protection on Kitchen Electrical Receptacle
B
K0912 K912: Have power receptacles that are properly grounded.
Short Summary

A kitchen electrical receptacle near the hand sink was found without required GFCI protection during an observation, and this deficiency was confirmed by the administrator and maintenance supervisor.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Deficiencies in Electrical Outlet Safety and Maintenance
D
K0912 K912: Have power receptacles that are properly grounded.
Short Summary

Surveyors found that an electrical outlet near a waterline was not GFI-protected, a damaged outlet faceplate was present in a resident room, and GFI outlets were not tested according to manufacturer instructions. Staff were unaware of these issues, and the deficiencies affected multiple residents and smoke compartments.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Non-Compliance with GFI Protection Near Water Sources
E
K0912 K912: Have power receptacles that are properly grounded.
Short Summary

The facility was found non-compliant with GFI protection requirements for power receptacles within six feet of a water source in three smoke zones. Observations revealed non-GFI protected outlets in the D Hall Nurses' Station Nourishment Area, B Hall Beauty Shop, and Main Kitchen Prep Area. This was confirmed by the Assistant DON and Maintenance Director.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Electrical Receptacle Deficiency in Laundry Room
B
K0912 K912: Have power receptacles that are properly grounded.
Short Summary

The facility failed to maintain electrical receptacles in compliance with safety standards in one of over thirty rooms. An observation revealed that the A wing resident laundry room had a washing machine without GFCI protection. This deficiency was confirmed by the maintenance supervisor.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Failure to Maintain GFI Protection Near Water Sources
D
K0912 K912: Have power receptacles that are properly grounded.
Short Summary

The facility did not ensure that power receptacles were GFI protected within six feet of a water source in one of the smoke zones. Observations revealed non-GFI protected outlets behind an ice machine near a resident room and in the Boiler/Generator Room. This was confirmed by the Administrator and Maintenance Director.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.

Know what gets cited — and walk into your next survey with full visibility

We process and analyze inspection reports and Plans of Correction using AI to surface insights and trends — so you can improve care quality and stay ahead of compliance risk before your next survey.

Get ready for your next survey

See what surveyors are citing in your state and spot your risk areas before they do.

Monthly Citation Reports

Have you been cited for this tag?

Save hours drafting a compliant Plan of Correction — AI built on real approved POCs.

Plan of Correction Writer

Trusted data from CMS and state health departments

Every citation, penalty and Plan of Correction is sourced from public CMS records (latest release June 24, 2026) and official state health department websites — never guesswork.

Trusted by long-term care providers and associations.

Allegria Senior Living logo
FHCA logo
WeCare Centers logo
Care Rehab logo
An unhandled error has occurred. Reload 🗙