K0223 K223: Provide exit doors that are held open by devices that will automatically close on the activation of a fire alarm or smoke detector.
E

Failure to Maintain Self-Closing Doors

Luther Woods Nursing And Rehabilitation CenterHatboro, Pennsylvania Survey Completed on 12-18-2024

Summary

The facility failed to maintain doors with self-closing devices on both levels of the building, as observed during a survey conducted on December 18, 2024. Several doors intended to be self-closing were found propped open or not functioning correctly. Specifically, the staff lounge ice room door was propped open with a door wedge, the A Wing lining closet door did not latch, and the B wing break room door was held open with a trash bag tied from the door handle to a handrail. Additionally, the chapel door was propped open with a chair, the sprinkler/janitor room door had a large gap between the door and frame when latched, the basement storage door was propped open with an installed kick down door stop, and the C wing clean lining door was propped open with a door stop. These deficiencies were confirmed during an exit interview with the Facility Administrator, Administrator in training, and the Director of Maintenance.

Plan Of Correction

All doorways will be kept closed at all times. Maintenance will do daily audits each day times 30 days. Then they will do weekly checks times 60 days. All stops whether portable or installed have been removed. A new door latch has been installed on the door on A Wing. A door will be installed at the Sprinkler Room as we have been unable to fix the gap. This will be completed by 1/30/25.

Penalty

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
See other K0223 citations
Fire-Rated Door in Hazardous Area Improperly Propped Open
K0223 K223: Provide exit doors that are held open by devices that will automatically close on the activation of a fire alarm or smoke detector.
Short Summary

Surveyors found that a fire-rated door leading to a hazardous dry storage room, protected by a one-hour fire barrier and equipped with a self-closing device, was held open by a bungee cord and obstructed by a storage rack, preventing it from self-closing and latching as required by NFPA 101. The Administrator confirmed the door should remain closed, and the deficiency was cited based on these observations.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Failure to Maintain Self-Closing Doors in Hazardous Area
E
K0223 K223: Provide exit doors that are held open by devices that will automatically close on the activation of a fire alarm or smoke detector.
Short Summary

Surveyors observed that the clean linen closet doors near room 216 were left open and did not close to a positive latch when tested, as confirmed by maintenance staff. These doors are required to be self-closing and kept closed unless held open by an approved device, and the failure to do so resulted in a deficiency.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Failure to Maintain Self-Closing Door Latching Mechanism
D
K0223 K223: Provide exit doors that are held open by devices that will automatically close on the activation of a fire alarm or smoke detector.
Short Summary

A corridor kitchen door equipped with a self-closing device was found not to latch when tested during a facility tour, as confirmed by the Maintenance Director. This deficiency impacted 32 residents in one smoke compartment and resulted in noncompliance with NFPA 101 standards for self-closing doors.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Failure to Maintain Self-Closing Doors
E
K0223 K223: Provide exit doors that are held open by devices that will automatically close on the activation of a fire alarm or smoke detector.
Short Summary

The facility failed to maintain two doors with self-closing devices, affecting one smoke compartment. Observations revealed that the doors at Nurse's Station 2 and Resident Room 62 did not positively latch into their frames. This issue was confirmed during an exit interview with the Facility Administrator and Facilities Manager.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Non-compliance with NFPA 101: Self-Closing Door Devices
D
K0223 K223: Provide exit doors that are held open by devices that will automatically close on the activation of a fire alarm or smoke detector.
Short Summary

The facility was found non-compliant with NFPA 101 standards as eight doors with self-closing devices were either missing door closers or held open with magnets not connected to the fire alarm system. These issues were identified during a fire safety tour and acknowledged by the Plant Operations Technician.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Non-compliance with Self-Closing Door Requirements
E
K0223 K223: Provide exit doors that are held open by devices that will automatically close on the activation of a fire alarm or smoke detector.
Short Summary

The facility was found non-compliant with NFPA 101 standards as a door in the Dietary Dry storage area was held open by a rubber wedge, affecting one of eight smoke compartments. This was confirmed during an exit interview with the Facility Administrator and Maintenance.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.

Know what gets cited — and walk into your next survey with full visibility

We process and analyze inspection reports and Plans of Correction using AI to surface insights and trends — so you can improve care quality and stay ahead of compliance risk before your next survey.

Get ready for your next survey

See what surveyors are citing in your state and spot your risk areas before they do.

Monthly Citation Reports

Have you been cited for this tag?

Save hours drafting a compliant Plan of Correction — AI built on real approved POCs.

Plan of Correction Writer

Trusted data from CMS and state health departments

Every citation, penalty and Plan of Correction is sourced from public CMS records (latest release June 24, 2026) and official state health department websites — never guesswork.

Trusted by long-term care providers and associations.

Allegria Senior Living logo
FHCA logo
WeCare Centers logo
Care Rehab logo
An unhandled error has occurred. Reload 🗙