K0281 K281: Install proper backup exit lighting.
F

Failure to Provide Continuous Egress Illumination

Rose Mountain Care CenterNew Brunswick, New Jersey Survey Completed on 12-12-2024

Summary

The facility failed to provide proper illumination for the means of egress, as required by NFPA 101: 2012 Edition, Sections 19.2.8 and 7.8. This deficiency was identified during observations and interviews conducted on December 3, 2024. Specifically, the Kitchen corridor, which is over 27 feet long leading to the exit door, lacked lighting when the switch was in the OFF position. Similarly, the East Hall and West Hall were observed to have no lighting when their respective switches were in the OFF position. These observations were confirmed by the staff present during the survey. The deficiency had the potential to affect all 83 residents in the facility. The facility's representatives were informed of this issue during the Life Safety Code survey exit conference on December 5, 2024.

Plan Of Correction

Rose Mountain Care Center Facility ID: 3145384 Survey completion date: 12-12-2024 K281 - (F) Illumination of means of Egress Element One: The lights in the kitchen corridor were immediately repaired to have continued lighting while the switch is in the OFF position. The lights in the East wing hall were immediately repaired to have continued lighting while the switch is in the OFF position. The lights in the West wing hall were immediately repaired to have continued lighting while the switch is in the OFF position. Element Two: This deficient practice had the potential to affect all residents. Element Three: The U.S. FOIA (b) (6) was educated on the requirements for continuous lighting even while the light switch is in the OFF position. Element Four: The Maintenance director / designee will audit the West wing, East wing, and the Kitchen corridors to ensure there is continuous lighting even while the light switch is in the OFF position monthly x3. Results will be reported to the QAPI team for review.

Penalty

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
See other K0281 citations
Failure to Ensure Continuous Illumination in Egress Pathway
D
K0281 K281: Install proper backup exit lighting.
Short Summary

The facility did not maintain continuous illumination in the Rehab corridor, as required by NFPA 101 standards. During a survey, it was found that turning off the wall-mounted light switches extinguished all lights in the corridor leading to an emergency stairwell exit. The Director of Maintenance confirmed the issue, noting that the lights would be continuous.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Failure to Illuminate Egress Pathways
E
K0281 K281: Install proper backup exit lighting.
Short Summary

The facility did not provide proper illumination for egress pathways, as required by NFPA 101. Observations revealed that exit doors from the French Quarter wing, the main entrance, and the Spanish Villa wing lacked necessary lighting for safe egress during darkness. These findings were confirmed by the Maintenance Director and acknowledged by the Administrator.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Inadequate Illumination of Egress Pathways
E
K0281 K281: Install proper backup exit lighting.
Short Summary

A Life Safety Code Survey found that the facility did not ensure proper illumination of egress pathways for four of seven exits. Observations revealed a lack of exterior lighting on several sections of the pathways. The Environmental Services Director was unaware of the deficiency but acknowledged the need for additional lighting.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Failure to Ensure Continuous Illumination in Egress Pathway
D
K0281 K281: Install proper backup exit lighting.
Short Summary

The facility did not maintain continuous illumination in the means of egress as required by NFPA 101. During a survey, it was found that turning off the wall-mounted light switches in the fifth-floor dining room also turned off all lights, including those needed for an emergency stairwell exit. This issue was identified on one of the three resident floors, and the Director of Maintenance confirmed the lights would be continuous.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Failure to Maintain Continuous Egress Illumination
E
K0281 K281: Install proper backup exit lighting.
Short Summary

The facility did not maintain continuous illumination of the means of egress in one of five stair towers. Light fixtures failed to illuminate the exit by Component 1, as observed and confirmed by the Director of Maintenance.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Failure to Maintain Illumination in Exit Stairways
E
K0281 K281: Install proper backup exit lighting.
Short Summary

The facility failed to maintain proper illumination in the exit stairways, affecting one of three floors. An observation revealed that the lights in the first floor South main stair tower were not illuminating. This was confirmed during an exit interview with the Administrator and the Maintenance Director.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.

Know what gets cited — and walk into your next survey with full visibility

We process and analyze inspection reports and Plans of Correction using AI to surface insights and trends — so you can improve care quality and stay ahead of compliance risk before your next survey.

Get ready for your next survey

See what surveyors are citing in your state and spot your risk areas before they do.

Monthly Citation Reports

Have you been cited for this tag?

Save hours drafting a compliant Plan of Correction — AI built on real approved POCs.

Plan of Correction Writer

Trusted data from CMS and state health departments

Every citation, penalty and Plan of Correction is sourced from public CMS records (latest release June 24, 2026) and official state health department websites — never guesswork.

Trusted by long-term care providers and associations.

Allegria Senior Living logo
FHCA logo
WeCare Centers logo
Care Rehab logo
An unhandled error has occurred. Reload 🗙