K0923 K923: Have proper medical gas storage and administration areas.
E

Improper Oxygen Cylinder Storage and Proximity to Combustibles

Christian Care Nursing CenterMuskegon, Michigan Survey Completed on 03-26-2025

Summary

The facility failed to comply with NFPA 99 requirements for the storage of nonflammable gases, specifically oxygen cylinders. During an observation, surveyors found that the oxygen storage closet in the main hall contained both full and non-full cylinders mixed together, rather than segregating empty cylinders from full ones as required. This was confirmed through an interview with the facility Maintenance Director at the time of observation. Additionally, the same oxygen storage closet was found to have combustibles stored within five feet of the oxygen cylinders, which is not permitted under the relevant fire safety standards. These deficiencies were identified during a survey and could potentially affect 17 occupants if the cylinders were needed during an emergency event. The report cites specific violations of NFPA 99 standards 11.6.5.2 and 11.3.2.3(2).

Plan Of Correction

K923 1. No residents were harmed as a result of this deficient practice. 2. The oxygen storage room has been appropriately organized and labeled in accordance with NFPA 99. All cardboard has been removed from the closet and signage has been introduced to keep the area clear. Proper storage racks and locations have clearly been labeled as to the placement of the oxygen containers. All clinical staff will be educated by 4/25/2025 regarding oxygen storage. 3. The QAPI Committee has directed the Director of Plant Operations/designee to perform weekly audits of the oxygen room to ensure compliance. The Administrator is responsible for ensuring that substantial compliance is attained through the Plan of Correction and is maintained thereafter. The results will be provided to the QAPI Committee for further follow-up and review.

Penalty

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
See other K0923 citations
Failure to Maintain Required Oxygen Cylinder Storage and Secured Storage Room
E
K0923 K923: Have proper medical gas storage and administration areas.
Short Summary

Surveyors found that oxygen storage requirements were not maintained when a freestanding oxygen cylinder was observed unsecured in a third-floor room and the C-Hall oxygen storage room door failed to close and latch due to a coordinator malfunction. The Maintenance Director confirmed these oxygen storage deficiencies during the survey exit interview.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Improper Storage of Oxygen Cylinders Near Combustibles
F
K0923 K923: Have proper medical gas storage and administration areas.
Short Summary

Surveyors observed that more than 12 "E" oxygen cylinders (18 total) were stored in a sprinkler room within five feet of combustible materials, contrary to NFPA 99 requirements for gas equipment cylinder storage. The Maintenance Director confirmed this storage practice during the survey. This noncompliance with NFPA 99 sections 11.3.1–11.3.3 was cited as a deficiency affecting all occupants in the event of a fire or other emergency.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Failure to Post Required Oxygen Storage Room Cautionary Signage
E
K0923 K923: Have proper medical gas storage and administration areas.
Short Summary

Surveyors found that an oxygen storage room on the second floor lacked the required precautionary signage stating, "CAUTION: OXIDIZING GAS(ES) STORED WITHIN NO SMOKING," as mandated for gas cylinder storage areas. This deficiency was confirmed by facility leadership during the initial survey and again during a subsequent revisit, when the same room was still missing the required sign.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Failure to Post Required Oxygen Storage Signage in Crash Cart Rooms
E
K0923 K923: Have proper medical gas storage and administration areas.
Short Summary

Surveyors found that oxygen cylinders were stored in crash cart rooms in two separate cores without the required precautionary signage on the doors indicating oxidizing gas storage and no smoking. Observations in two smoke compartments showed oxygen cylinders present in the 3 East and 2 East core crash cart rooms, yet the doors lacked the mandated "CAUTION: OXIDIZING GAS(ES) STORED WITHIN NO SMOKING" signage. The facility administrator and maintenance leadership confirmed that the proper oxygen storage signs were not posted on these doors.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Improper Oxygen Cylinder Storage Near Combustibles and Electrical Receptacles
E
K0923 K923: Have proper medical gas storage and administration areas.
Short Summary

Surveyors found that oxygen cylinders stored within first- and second-floor nurses' stations were placed less than five feet from electrical receptacles and combustible materials, in violation of NFPA 99/101 requirements for separation of oxidizing gases from combustibles and ignition sources. The Administrator and Maintenance Director confirmed during interview that the cylinders were improperly stored in proximity to these combustible and ignition sources.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Improper Storage and Security of Gas Cylinders
D
K0923 K923: Have proper medical gas storage and administration areas.
Short Summary

Surveyors found that gas cylinders were improperly stored and unsecured, with 38 cylinders in an outside storage room lacking the required oxidizing gas signage and with full and empty cylinders comingled, and an additional 25 cylinders stored adjacent to this area without any means to prevent unauthorized access. During an interview, the Maintenance Director acknowledged the issues and reported being unaware of the specific NFPA 99 storage requirements.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.

Know what gets cited — and walk into your next survey with full visibility

We process and analyze inspection reports and Plans of Correction using AI to surface insights and trends — so you can improve care quality and stay ahead of compliance risk before your next survey.

Get ready for your next survey

See what surveyors are citing in your state and spot your risk areas before they do.

Monthly Citation Reports

Have you been cited for this tag?

Save hours drafting a compliant Plan of Correction — AI built on real approved POCs.

Plan of Correction Writer

Trusted data from CMS and state health departments

Every citation, penalty and Plan of Correction is sourced from public CMS records (latest release June 24, 2026) and official state health department websites — never guesswork.

Trusted by long-term care providers and associations.

Allegria Senior Living logo
FHCA logo
WeCare Centers logo
Care Rehab logo
An unhandled error has occurred. Reload 🗙